Fluke 1503 Insulation Resistance Tester

Fluke 1503 Insulation Resistance Tester is compact, rugged, reliable, and easy to use.

With its multiple test voltages, the tester is ideal for many troubleshooting, commissioning, and preventative maintenance applications.

Overview

Live circuit detection prevents insulation tester.

Fluke 1503 Insulation Resistance Tester is compact, rugged, reliable, and easy to use. Repetitive or hard-to-reach testing is easy with the remote test probe.

With its multiple test voltages, the tester is ideal for many troubleshooting, commissioning, and preventative maintenance applications.

The tester has an insulation test range of 0.1 MΩ to 2000 MΩ and insulation test voltages 500V and 1000V.

1503 insulation resistance tester features an AC/DC voltage of 0.1V to 600V, 200 mA continuity, the resistance of 0.01 MΩ to 20.00 MΩ.

Auto power off to maximize battery life, auto-discharge of capacitive voltage for added user protection and large backlit display for easy read measurements.

From industrial electronic installation, maintenance and service, to calibration and quality control. Fluke tools help keep business and industry around the globe up and running.

Those wonder fluke product now in Bangladesh. Fluke Bangladesh makes the way that you always want for.Very easy to get your best fluke product in Bangladesh.

Features

  • Insulation test range 0.1 MΩ to 2000 MΩ
  • Insulation test voltages 500 V, 1000 V
  • Repetitive or hard-to-reach testing is easy with the remote test probe
  • Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
  • Auto-discharge of capacitive voltage for added user protection
  • AC/DC voltage: 0.1 V to 600 V
  • 200 mA Continuity
  • Resistance: 0.01 Ω to 20.00 kΩ
  • Save battery power with auto power off
  • Read measurements easily with large, backlit display
  • CAT IV 600 V overvoltage category rating for added user protection
  • A remote probe, test leads, probes and alligator clips included with each tester
  • Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
  • Four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests
  • One year warranty

Specifications

AC/DC Voltage Measurement
Accuracy Range 600.0 V
Resolution 0.1 V
50 Hz to 400 Hz ±(% of Rdg + Digits) ±(2% + 3)
Input impedance 3 MΩ (nominal), < 100 pF
Common mode rejection ratio (1 kΩ unbalanced) > 60 dB at DC, 50 or 60 Hz
Overload protection 600 V rms or DC
Earth Bond Resistance Measurement
Range/Resolution 20.00 Ω 0.01 Ω
200.0 Ω 0.1 Ω
2000 Ω 1.0 Ω
20.00 kΩ 0.01 kΩ
Accuracy ±(1.5% + 3)
Overload protection 2 V rms or DC
Open circuit test voltage > 4.0 V, < 8 V
Short circuit current > 200.0 mA
Insulation Specifications
Measurement range 0.01 MΩ to 2000 MΩ
Test voltage 500 V, 1000 V
Test voltage accuracy + 20%, – 0%
Short circuit current 1 mA nominal
Auto discharge Discharge time < 0.5 second for C = 1 µF or less
Live circuit indicator Inhibit test if terminal voltage > 30 V prior to initialization of test
Maximum capacitive load Operable with up to 1 µF load
Measure accuracy
500 V ±(1.5% + 5)
1000 V ±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ
General Specifications
Maximum voltage applied to any terminal: 600 V AC rms or DC
Storage temperature -40°C to 60°C (-40°F to 140°F)
Operating temperature -20°C to 55°C (-4°F to 131°F)
Temperature coefficient 0.05 x (specified accuracy) per °C for temperatures < 18°C or > 28°C (< 64°F or > 82°F)
Relative humidity
0% to 95% @ 10°C to 30°C (50°F to 86°F)
0% to 75% @ 30°C to 40°C (86°F to 104°F)
0% to 40% @ 40°C to 55°C (104°F to 131°F)
Vibration Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
Shock 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor)
Electromagnetic compatibility In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997)
Safety Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV)
Certifications CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition
Batteries Four AA batteries (NEDA 15A or IEC LR6)
Battery llife Insulation test use: Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
Resistance measurements: Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25 seconds off.
Size (H x W x L) 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in)
Weight 550 g (1.2 lb)
IP rating IP40
Altitude Operating 2000 m CAT IV 600 V, 3000 m CAT III 600 V
Non-operating (storage) 12,000 m
Over-range capability 110% of range
Included accessories TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe

Includes

  • Remote probe
  • Test probes
  • Test leads
  • Alligator clips
  • User documentation

Resources

Fluke 1503 Insulation Resistance Tester – Catalog    Download

Accessories

Test Leads
-
Fluke TL225 SureGrip Stray Voltage Adapter Test Lead Kit TL225

Voltage Adapter Test Lead Kit makes sure the meter has a low input impedance that eliminates stray voltages and indicates real voltage.


Cases and Holsters
-
Fluke C25 Large Soft Case for Digital Multimeters C25

The C25 carrying case is a durable, zippered carrying case with padding and inside pocket, and high quality polyester exterior. It includes a convenient hand strap and carries most of Fluke’s popular digital multimeters.


-
Fluke CXT170 CXT170

Rugged Pelican Hard Case for the Fluke 170 Series.


-
Fluke TPAK ToolPak Magnetic Meter Hanger ToolPak

Attaches to back of a Fluke 110/170/180 Series Meter, 20/70-III with integrated holster (with adapter), 724/725, and 50 Series II.

Reviews

There are no reviews yet.

Be the first to review “Fluke 1503 Insulation Resistance Tester”

Your email address will not be published. Required fields are marked *