Fluke 1550c 5kv insulation tester

Fluke 1550C offers digital insulation testing up to 5 kV, making it ideal for testing high voltage equipment including switchgear, motors, and cables.

1550C insulation resistance tester offers digital insulation testing up to 5 kV, making them ideal for testing.

Overview

Performing the PI and DAR calculations, while out in the field, can be a pain, but 1507 can perform the calculations for you, greatly enhancing an electrician’s troubleshooting abilities.

Fluke 1550C offers digital insulation testing up to 5 kV, making it ideal for testing high voltage equipment including switchgear, motors, and cables.

The Fluke 1550C insulation resistance tester offers digital insulation testing up to 5 kV, making them ideal for testing.

Fluke 1550C is an insulation tester with preset and adjustable test voltages for measuring insulation resistance to 1TΩ (2TΩ for 10kV models) to indicate the condition of windings or cables in motors, switchgears, electrical installations, and other insulated equipment, and it also measures leakage current to 2 milliamperes (mA), capacitance to 20μF, and AC and DC voltage to 600V.

For improved accuracy during high-resistance testing, the guard terminal eliminates interference from leakage current. The meter has an LCD that shows the reading numerically and in a bar graph.
For better Maintenance surely you can use Fluke 1550C Insulation Tester.

Very fantastic scope in Bangladesh for Fluke client in Bangladesh. Surely now You can find world-class Fluke product in Bangladesh.

Features

  • Test voltages to up 5 kV
  • CAT III 1000 V, CAT IV 600 V safety rating
  • Warning function alerts the user that line voltage is present and gives the voltage reading up to 600 V AC or DC for increased user safety
  • Selectable test voltages in 50 V steps from 250 V to 1000 V, and 100 V steps above 1000 V
  • Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall
  • Long battery life gives the user over 750 tests between charges
  • Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI) with no additional setup
  • Guard system eliminates the effect of surface leakage current on high-resistance measurements
  • Large digital/analog LCD for easy viewing
  • Capacitance and leakage current measurement
  • Ramp function for breakdown testing
  • Resistance measurements up to 2 TΩ
  • Timer settings up to 99 minutes for timed tests

Specifications

Electrical Specifications
The tester’s accuracy is specified for one year after calibration at operating temperatures of 0°C to 35°C. For operating temperatures outside the range (-20°C to 0°C and 35°C to 50°C), add ± .25% per °C, except on the 20% bands add ± 1% per °C.
Insulation Resistance Measurement
Test voltage (DC)
250 V Range < 250 kΩ,
250 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
500 V Range < 500 kΩ
500 kΩ to 10 GΩ
10 GΩ to 100 GΩ
> 100 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
1000 V Range < 1 MΩ
1 MΩ to 20 GΩ
20 GΩ to 200 GΩ
> 200 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
2500 V Range < 2.5 MΩ
2.5 MΩ to 50 GΩ
50 GΩ to 500 GΩ
> 500 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
5000 V Range < 5 MΩ
5 MΩ to 100 GΩ
100 GΩ to 1 TΩ
> 1 TΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
Bar graph range 0 to 1 TΩ (1550C) – 0 to 2 TΩ (1555)
Insulation test voltage accuracy -0%, +10% at 1 mA load current
Induced AC mains current rejection 2 mA maximum
Charging rate for capacitive load 5 seconds per μF
Discharge rate for capacitive load 1.5 s/μF
Leakage current measurement Range 1 nA to 2 mA
Accuracy ± (5% + 2 nA)
Capacitance measurement Range 0.01 μF to 15.00 μF
Accuracy ± (15% rdg + 0.03 μF)
Timer Range 0 to 99 minutes
Resolution setting 1 minute
Resolution indication 1 second
Live circuit warning Warning range 30 V to 660 V AC/DC, 50/60 Hz
Voltage accuracy ± (15% + 2 V)
Software specifications FlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8.
General Specifications
Display 75 x 105 mm
Power 12 V lead-acid rechargeable battery, Yuasa NP2.8-12
Charger Input (AC) 85 V to 250 V AC 50/60 Hz 20 VA
This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only.
Dimensions 269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in)
Weight 3.7 kg (8.2 lb)
Temperature (operating) -20°C to 50°C (-4°F to 122°F)
Temperature (storage) -20°C to 65°C (-4°F to 149°F)
Humidity 80% to 31°C decreasing linearly to 50% at 50°C
Altitude 2000 m
Enclosure sealing IP40
Input overload protection 1000 V AC
Electromagnetic compatibility EN 61326
Safety compliance IEC 61010-1: Overvoltage category II, Pollution Degree 2.
IEC 61010-2-030: Measurement 600V CAT IV / 1000V CAT III
IEC 61557-1, IEC 61557-2

Includes

  • Test cables with alligator clips (red, black, green)
  • Infrared adapter with interface cable
  • FlukeView® Forms Basic CD-ROM
  • AC power cord
  • Soft carrying case
  • English manual
  • User’s manual on CD-ROM
  • Quick reference card
  • Software license agreement
  • Registration card
  • FlukeView® Forms installation guide
  • USB-IR cable installation guide
  • Heavy duty alligator clip leads

Resources

Fluke 1550c 5kv insulation tester – Catalog    Download

Accessories

Communications
-
Fluke pc3000 FC Adapter and Software PC3000-FC

This USB adapter and software allows your PC or laptop to communicate with up to 10 Fluke Connect wireless devices.


Test Leads, Probes and Clips
-
Fluke TL1550EXT Extended Test Lead Set – 25 foot TL1550EXT

Reviews

There are no reviews yet.

Be the first to review “Fluke 1550c 5kv insulation tester”

Your email address will not be published. Required fields are marked *